KOEL Green Gensets

Liquid Cooled (320-625kVA)

Prime Rating at rated rpm ( as per ISO8528)1 kVA 320 HD 380 HD 400 HD 500 HD 600 HD 625 HD
kW 256 304 320 400 480 500
Genset Model KG1-320WS KG1-380WS KG1-400WS KG1-500WS KG1-600WS KG1-625WS
Frequency Hz 50 50 50 50 50 50
Power factor lagging 0.8 0.8 0.8 0.8 0.8 0.8
Voltage V 415 3Ø 415 3Ø 415 3Ø 415 3Ø 415 3Ø 415 3Ø
Governing class ( As per ISO 8528 Part-V) G3 G3 G3 G3 G3 G3
Noise level dBA < 75 < 75 < 75 < 75 < 75 < 75
Fuel Consumption* At 100 % Load Ltrs/Hr 73 85.8 89.5 111 132 137
At 75 % Load 53 62.4 65.1 83.2 99 102.7
At 50 % Load 37.6 44.1 >46.0 57.1 67.9 70.4
Fuel Tank Capacity Ltrs 850 850 850 990 990 990
Overall dimensions of genset (L x W x H)^ mm 5100 x
2000 x
2408
5375 x
2000 x
2408
5375 x
2000 x
2408
5650 x
2000 x
2558
6660 x
2000 x
2710
6660 x
2000 x
2710
Dry weight of genset with canopy (approx..)^ Kg 5910 6000 6050 7200 7700 7800
Wet weight of genset with canopy (approx..)^ Kg 6650 6750 6800 8050 8550 8650
Height including Silencer mm 2908 2943 2943 3177 3420 3420
Electrical Battery starting voltage Volts-DC 24 24 24 24 24 24
ENGINE
Engine Model DV8TA G1 DV8TA G2 DV8TA G3 DV10TA G1 DV12TA G1 DV12TA G2
Rated output (Prime Continuous rating as per ISO 8528-1) kW 294 346 360 447 532 552
HP 400 470 490 608 723 750
Number of Cylinder Number 8 8 8 10 12 12
Cubic capacity 2 Ltrs 15.92 15.92 15.92 19.90 23.88 23.88
Bore x Stroke mm 130 x 150 130 x 150 130 x 150 130 x 150 130 x 150 130 x 150
Rated Speed RPM 1500 1500 1500 1500 1500 1500
Aspiration NA/TC/TA TA TA TA TA TA TA
Lube Oil change period hrs. 500 500 500 500 500 500
Lube oil Sump Capacity Ltrs 41.0 41.0 41.0 45.0 50.0 50.0
Coolant Capacity Ltrs 60.0 112.0 112.0 120.0 135.0 135.0
ALTERNATOR
Insulation Class Class H
Alternator Efficiency (at 100% load) 0.8 pf** 93.8 94.0 94.1 94.8 95.5 95.7
Alternator Efficiency (at 75% load) 0.8 pf** 94.3 94.4 94.7 95.3 95.8 96.0
Permissible Voltage Dip at Full Load 0.8 pf Lag < 20 % < 19 % < 19 % < 19 % < 19 % < 19 %
Time Permitted to build up rated voltage at Rated RPM < 5 sec provided engine reach the rated speed
Short Circuit Ratio 0.55 0.35 0.45 0.45 0.37 0.36
Short Circuit With Stand Time sec < 3 sec
Overload With Stand Capacity % 10% overload for one hour once in 12 hours
For intermediate ratings, kindly contact nearest KOEL office
Notes
^ Tolerances Apply
* With 0.845 Specific Gravity of diesel ( 5% Tolerance )
** Efficiency of Alternator as per standards IS 4722 and IEC 34-1 For Site Conditions other than standard operating conditions consult KOEL for available prime power.

Prime rating and Stand-by rating1

'Prime power' is designed for Unlimited hours, as compared to 'Emergency stand-by' designed for 200 hours in a year. Prime rated Gensets also permit 10% temporary overloading. Users need to carefully select the Genset rating to meet their requirement. KOEL offers Prime power as standard offer. Contact KOEL for stand-by ratings.

Engine capacity does matter2

Engine capacity (cc) plays a vital role in Genset performance. Higher engine capacity leads to a robust and stable Genset performance.

Higher engine capacity also enables Genset to respond quickly & positively to sudden load additions.

1. Canopy

  • Ease of Access and Serviceability
  • Aesthetically designed, weather and sound resistant enclosure
  • Insulation conforms to UL94-HF1 class for flammability

2. Controller

  • Microprocessor based fully configured
  • Graphical bigger LCD display
  • Best in class monitoring and diagnostic
  • Integrable with AMF, synchronization & communication configurations

3. Engine

  • O2E Series: Low emission, high efficiency engines
  • Compact, Robust and Rugged Design
  • 500 hours lube-oil change period

4. Alternator

  • Best In Class Efficiency
  • Special Windings to Reduce Harmonics
  • Vacuum Pressure Impregnation and epoxy gel coating on winding

Monitoring Features

  • Phase Voltages & Currents, Frequency, Reverse power, Genset kVA , KW, KVAr , KWH, Power Factor, Canopy Temperature
  • Lube oil Pressure, Engine Temperature RPM, Run Hours, No. of starts, Fuel Level, Auto / Manual Stop, AMF feature
  • Battery charge condition
  • Modbus communication, Remote Monitoring

Optional Features

  • Synchronization

Diagnostic Features

  • Battery charging failure, Over/Under speed, Over Current, Over/Under Voltage, Over KW, Phase Seq., Phase missing, Mains Under voltage, Earth Fault trip, Fuel level Alarm
  • Low lube oil Pressure, High Engine Temperature, Low/High battery voltage, Low Fuel Level, Over Crank protection, Routine Maint. indicator, Genset Test Facility, Mains Frequency, Fail to crank

Being in control of your Genset is certainly a winning edge!